EPA 608 Type III study guide: low pressure

Type III covers low-pressure appliances, mainly centrifugal chillers using refrigerants like R-123. These systems run partly in a vacuum, so the rules are different.

How low-pressure systems are different

  • Low-pressure refrigerants (R-11, R-123) boil above 50°F at atmospheric pressure, so parts of the chiller run below atmospheric pressure.
  • Leaks pull air and moisture in instead of letting refrigerant out. The purge unit removes those noncondensables. A purge that runs too often is a classic sign of a leak.
  • Moisture inside forms acids with the refrigerant.
  • Most low-pressure chillers use centrifugal compressors.
  • The rupture disc on the evaporator is typically set at 15 psig.

Leak testing

  • To leak-test, raise the pressure with controlled hot water or heating blankets. If you use nitrogen, never exceed 10 psig, because the rupture disc is set at 15.
  • A standing vacuum test that shows a steady rise means a leak or moisture boiling off.

Recovery and charging

  • Recover liquid first, then recover the vapor down to 25 mm Hg absolute.
  • Keep water circulating through the tubes, or drain them, during recovery and evacuation so they don't freeze and crack.
  • Heat the oil before draining it to release refrigerant dissolved in it.
  • When charging an evacuated chiller, add vapor first until the saturation temperature is above freezing, then switch to liquid. Charge through the evaporator charging valve.

Safety and leak repair

  • R-123 is B1: higher toxicity, no flame propagation. ASHRAE 15 requires a refrigerant monitor in the equipment room.
  • Comfort-cooling chillers with 50 pounds or more of ozone-depleting refrigerant must be repaired when the leak rate exceeds 10%, generally within 30 days.
  • Leaking 125% or more of the full charge in a year must be reported to EPA.

Numbers to memorize

FactAnswer
Low-pressure boiling pointAbove 50°F at atmospheric
Max leak-test pressure10 psig
Rupture disc setting15 psig
Required evacuation level25 mm Hg absolute
Recovery orderLiquid first, then vapor
Charging orderVapor first, then liquid
Comfort cooling leak trigger10%
Repair deadline30 days
Chronic leaker report125% of charge in a year
Ready? Take a full 25-question Type III practice test with explanations. Start now →

HVAC Tips for Technicians

See it done for real

Watch it on a real job

Reading the rule is one thing. Here's what it looks like in the field, with the tools in my hands.

More in HVAC Tips for Technicians

Keep going

The tools and training I built for techs.

App

AC Tool Pro

PT charts, superheat and subcooling, diagnostics in cooling and heating, airflow and BTU calculators, and a 3D view of every component. Used by 200+ techs.

$20/mo or $200/yr
Get AC Tool Pro
App · Español

AC Tool Pro Latino

La misma herramienta de AC Tool Pro, completamente en español, para técnicos hispanohablantes.

Ver AC Tool Pro Latino
Video course

Mini Split Training

The full mini split course: how they work, maintenance, repair, sizing and install. 45 videos, quizzes and a certificate.

$49.99/mo or $299/yr
Start the course
Book

Mini Split Training (Paperback)

A 108-page full-color field manual with real photos, component testing, multi-zone, and 200+ practice questions.

$39.99 on Amazon
Get the book

Common questions

Who needs Type III?

Techs who work on low-pressure centrifugal chillers, usually in commercial and industrial buildings. If you want Universal, you need it too.

What's the most-missed Type III fact?

The pressure limits: never pressurize above 10 psig for a leak test, because the rupture disc opens at 15 psig.

Other study guides: Core · Type I · Type II