Home › Study guides › Type II
EPA 608 study guideEPA 608 Type II study guide: high pressure
Type II covers high- and very high-pressure appliances, except small appliances and car AC: split systems, heat pumps, mini splits, rooftop units and commercial refrigeration. It's the certification most HVAC techs need.
Pressure classes
- High-pressure refrigerants boil between -58°F and 50°F at atmospheric pressure: R-22, R-410A, R-404A, R-407C, R-32, R-454B.
- Very high-pressure refrigerants boil below -58°F: R-13, R-23, R-503.
Required evacuation levels
Before opening a system for a major repair or disposal, recover to these levels (inches of mercury vacuum):
| Appliance | Equipment before Nov 15, 1993 | Equipment on/after Nov 15, 1993 |
|---|---|---|
| R-22, under 200 lb | 0 | 0 |
| R-22, 200 lb or more | 4 | 10 |
| Other high-pressure, under 200 lb | 4 | 10 |
| Other high-pressure, 200 lb or more | 4 | 15 |
| Very high-pressure | 0 | 0 |
- A major repair means removing the compressor, condenser, evaporator or auxiliary heat exchanger coil.
- For a non-major repair that isn't followed by an evacuation to the environment, evacuate to at least 0 psig.
- After reaching the target vacuum, wait a few minutes. If the pressure rises, liquid or refrigerant in the oil is still in the system, so keep recovering.
- System-dependent recovery equipment can only be used on appliances with 15 pounds or less.
Leak detection and repair
- Signs of a leak: oil residue at joints, fittings and flare nuts. Before charging, pressurize with dry nitrogen (with a trace of refrigerant if using an electronic detector).
- Under the Section 608 rules for ozone-depleting refrigerant, appliances with 50 pounds or more must be repaired when the leak rate exceeds:
| Appliance type | Leak rate trigger |
|---|---|
| Comfort cooling | 10% |
| Commercial refrigeration | 20% |
| Industrial process refrigeration | 30% |
| All other appliances | 10% |
- Repair within 30 days (120 days if industrial process refrigeration needs a shutdown), or develop a retrofit/retirement plan within 30 days and complete it within 1 year.
- Do initial and follow-up verification tests after the repair.
- An appliance leaking 125% or more of its full charge in a calendar year must be reported to EPA.
- Keep service and leak records for 3 years.
New for HFCs: starting January 1, 2026, EPA's 2024 HFC rule applies leak repair requirements to certain appliances with 15 pounds or more of HFC refrigerant. Details on EPA.gov.
Recovery techniques and safety
- Recover liquid first. On systems with a large liquid charge, the push-pull method moves liquid fast: vapor pulled from the recovery cylinder pushes liquid out of the system.
- Noncondensables collect in the condenser and raise head pressure.
- Never energize a hermetic compressor in a deep vacuum. The motor windings can arc and short.
- ASHRAE 15 sets equipment room safety requirements, including refrigerant detectors, alarms and ventilation.
Numbers to memorize
| Fact | Answer |
|---|---|
| R-22 under 200 lb (new equipment) | 0 in Hg |
| R-22 200 lb+ (new equipment) | 10 in Hg |
| Other high-pressure under 200 lb (new) | 10 in Hg |
| Other high-pressure 200 lb+ (new) | 15 in Hg |
| Very high-pressure | 0 in Hg |
| Non-major repair | 0 psig |
| System-dependent recovery limit | 15 lb or less |
| ODS leak repair applies at | 50 lb or more |
| Comfort cooling / commercial / IPR triggers | 10% / 20% / 30% |
| Repair deadline | 30 days |
| Chronic leaker report | 125% of charge in a year |
| Records kept | 3 years |
| HFC leak repair (from Jan 1, 2026) | 15 lb or more |
How to Replace a Leaking Condenser Coil
Watch it on a real job
Reading the rule is one thing. Here's what it looks like in the field, with the tools in my hands.
More in HVAC Tips for TechniciansKeep going
The tools and training I built for techs.
AC Tool Pro
PT charts, superheat and subcooling, diagnostics in cooling and heating, airflow and BTU calculators, and a 3D view of every component. Used by 200+ techs.
AC Tool Pro Latino
La misma herramienta de AC Tool Pro, completamente en español, para técnicos hispanohablantes.
Ver AC Tool Pro LatinoMini Split Training
The full mini split course: how they work, maintenance, repair, sizing and install. 45 videos, quizzes and a certificate.
Mini Split Training (Paperback)
A 108-page full-color field manual with real photos, component testing, multi-zone, and 200+ practice questions.
Common questions
Is Type II the hardest section?
Many techs say so, because of the evacuation table and the leak repair numbers. Learn the table above cold and take the Type II practice test until you're consistently over 20.
Does Type II cover mini splits?
Yes. Mini splits are high-pressure appliances (R-410A, R-32, R-454B), so working on them requires Type II or Universal.