EPA 608 study guide

EPA 608 Core study guide

Everyone takes Core. It covers why the rules exist, what the rules are, and how to handle refrigerant safely. Pass Core plus at least one Type to get certified.

Ozone depletion and refrigerant families

The ozone layer in the stratosphere blocks harmful UV radiation. When refrigerants containing chlorine reach the stratosphere, the chlorine breaks ozone apart, and a single chlorine atom can destroy thousands of ozone molecules. Less ozone means more UV at ground level: more skin cancer, more cataracts, and damage to crops and sea life.

  • CFCs (R-11, R-12, R-502): the most chlorine and the highest ozone depletion potential (ODP). Production ended January 1, 1996.
  • HCFCs (R-22, R-123): contain less chlorine but still deplete ozone. New R-22 production ended January 1, 2020.
  • HFCs (R-410A, R-134a, R-32): no chlorine, zero ODP, but a high global warming potential (GWP), so they're being phased down under the AIM Act.
  • HFOs (R-1234yf) and HFO blends (R-454B): zero ODP and low GWP.

The law: Clean Air Act, Montreal Protocol and Section 608

  • The Montreal Protocol is the international treaty to phase out ozone-depleting substances. The U.S. carries it out through the Clean Air Act.
  • Venting is illegal. Knowingly releasing CFCs and HCFCs has been banned since July 1, 1992, and substitutes like HFCs since November 15, 1995. Only de minimis releases, the small amounts released during good-faith recovery and hose connections, are allowed.
  • Fines are assessed per day, per violation, and EPA can pay up to $10,000 to someone whose information leads to a conviction.
  • Certification: you must be certified to open a refrigerant circuit. Apprentices are exempt only while a certified tech closely and continually supervises them. EPA doesn't issue cards; an EPA-approved certifying organization does. Certification never expires.
  • Sales restriction: only certified technicians may buy refrigerant for servicing stationary equipment, with limited exceptions.
  • Recovery equipment made after November 15, 1993 must be certified by an EPA-approved testing organization and have low-loss fittings.

Recover, recycle, reclaim

TermWhat it means
RecoverRemove refrigerant from a system and store it in an external container. No testing or processing.
RecycleClean refrigerant for reuse, usually by separating oil and running it through filter-driers. Typically done on site.
ReclaimReprocess refrigerant to AHRI 700 new-product purity, verified by chemical analysis. Only an EPA-certified reclaimer can do it.

Recovered or recycled refrigerant may go back into equipment owned by the same owner. If it changes owners, it must be reclaimed. Never mix different refrigerants in one cylinder; mixed refrigerant may be impossible to reclaim.

Faster recovery: recover liquid first, use short, large-diameter hoses, remove Schrader cores, and keep the recovery cylinder cool.

Refrigeration basics, blends and oils

  • The compressor sends out high-pressure, high-temperature vapor; the condenser rejects heat; the metering device drops pressure; the evaporator absorbs heat.
  • For saturated refrigerant, pressure and temperature are linked, and a PT chart tells you one from the other.
  • On gauges, the blue compound gauge reads low-side pressure and vacuum, and the red gauge is the high side.
  • Zeotropic blends (400-series, like R-410A) have temperature glide and can fractionate, so charge them as liquid. Azeotropic blends (500-series) act like one refrigerant.
  • There are no true drop-in replacements. HFCs use POE oil, which soaks up moisture fast.
  • Evacuation removes air and moisture after a system has been opened. Moisture left in the system forms acids and sludge. A micron gauge measures deep vacuum.

Safety and cylinders

  • Refrigerant vapor is heavier than air. It can push out oxygen in low or enclosed spaces and cause suffocation.
  • Liquid refrigerant causes frostbite, so wear safety glasses and gloves.
  • Leak-test with dry nitrogen (a trace of refrigerant is OK for detection). Never oxygen or compressed air, because oxygen can explode in contact with oil.
  • Recovery cylinders are gray with a yellow top. Fill them to no more than 80% by weight, evacuate new ones before first use, and have them retested every 5 years.
  • Never heat a cylinder above 125°F. Disposable cylinders are never refilled: recover what's left, then render them useless before recycling the metal.

Newer rules: EPA's 2024 HFC rule added leak repair requirements starting January 1, 2026 for certain appliances with 15 pounds or more of HFC refrigerant. Check EPA.gov for current details.

Numbers to memorize

FactAnswer
Venting ban: CFCs and HCFCsJuly 1, 1992
Venting ban: substitutes (HFCs)November 15, 1995
CFC production endedJanuary 1, 1996
New R-22 production endedJanuary 1, 2020
Recovery cylinder max fill80% by weight
Recovery cylinder colorGray body, yellow top
Cylinder retestEvery 5 years
Never heat a cylinder above125°F
EPA informant awardUp to $10,000
Reclaimed refrigerant standardAHRI 700
Certification expiresNever
Passing score18 of 25 (72%)
Ready? Take a full 25-question Core practice test with explanations. Start now →

How to Recover, Vacuum, and Charge a Mini Split

See it done for real

Watch it on a real job

Reading the rule is one thing. Here's what it looks like in the field, with the tools in my hands.

More in HVAC Tips for Technicians

Keep going

The tools and training I built for techs.

App

AC Tool Pro

PT charts, superheat and subcooling, diagnostics in cooling and heating, airflow and BTU calculators, and a 3D view of every component. Used by 200+ techs.

$20/mo or $200/yr
Get AC Tool Pro
App · Español

AC Tool Pro Latino

La misma herramienta de AC Tool Pro, completamente en español, para técnicos hispanohablantes.

Ver AC Tool Pro Latino
Video course

Mini Split Training

The full mini split course: how they work, maintenance, repair, sizing and install. 45 videos, quizzes and a certificate.

$49.99/mo or $299/yr
Start the course
Book

Mini Split Training (Paperback)

A 108-page full-color field manual with real photos, component testing, multi-zone, and 200+ practice questions.

$39.99 on Amazon
Get the book

Common questions

What's the hardest part of Core?

Most people miss the dates and the recover/recycle/reclaim definitions. Memorize the table above and take the Core practice test until you're scoring 22 or better.

Can I take Core open-book?

Core taken open-book can't count toward Universal. For Universal, Core must be proctored.

Other study guides: Type I · Type II · Type III