EPA 608 study guideEPA 608 Type I study guide: small appliances
Type I certifies you to recover refrigerant from small appliances: equipment manufactured, charged and hermetically sealed at the factory with 5 pounds of refrigerant or less.
What counts as a small appliance
A small appliance is manufactured, charged and hermetically sealed at the factory with 5 pounds or less of refrigerant. Examples: household refrigerators and freezers, window AC units, PTACs, dehumidifiers, water coolers, vending machines and ice makers.
Not Type I: car AC (MVAC) falls under Section 609, and residential split systems are Type II.
Recovery requirements
| Recovery equipment | Compressor runs | Compressor doesn't run |
|---|---|---|
| Made before Nov 15, 1993 | 80% | 80% |
| Made on or after Nov 15, 1993 | 90% | 80% |
Or, in either case, evacuate the small appliance to 4 inches of mercury vacuum. Equipment made after November 15, 1993 must be certified by an EPA-approved testing organization.
Recovery methods
- Self-contained (active) recovery equipment has its own compressor.
- System-dependent (passive) recovery uses the appliance's compressor or the system's own pressure.
- If the compressor doesn't run, access both the high and low sides, and heat and gently tap the compressor to free refrigerant trapped in the oil.
- Piercing access valves are fine for recovery, but leak-check them and don't leave solderless ones on as permanent fittings; they tend to leak over time.
- Identify the refrigerant from the nameplate. With the unit off and at room temperature, the pressure should match the PT chart. Higher pressure means noncondensables (air) or the wrong refrigerant.
Safety and disposal
- Refrigerant hitting an open flame or hot surface can break down into toxic gases like phosgene and acids. Ventilate, and keep flames away.
- Some new small appliances use R-600a (isobutane) or R-290 (propane), both A3 (highly flammable). Use equipment rated for flammable refrigerants and remove ignition sources.
- The final person in the disposal chain (scrap yard, recycler, landfill) must make sure the refrigerant was removed, often with a signed statement from whoever recovered it.
About the Type I test: Type I may be taken open-book without a proctor, but then the passing score is 84%, and it can't count toward Universal. Proctored, it's 18 of 25.
Numbers to memorize
| Fact | Answer |
|---|---|
| Small appliance charge | 5 lb or less, factory sealed |
| Post-1993 equipment, compressor running | Recover 90% |
| Post-1993 equipment, compressor not running | Recover 80% |
| Pre-1993 equipment | Recover 80% |
| Or evacuate to | 4 inches Hg vacuum |
| Car AC is covered by | Section 609 |
| Open-book Type I passing score | 84% |
How to Recover, Vacuum, and Charge a Mini Split
Watch it on a real job
Reading the rule is one thing. Here's what it looks like in the field, with the tools in my hands.
More in HVAC Tips for TechniciansKeep going
The tools and training I built for techs.
AC Tool Pro
PT charts, superheat and subcooling, diagnostics in cooling and heating, airflow and BTU calculators, and a 3D view of every component. Used by 200+ techs.
AC Tool Pro Latino
La misma herramienta de AC Tool Pro, completamente en español, para técnicos hispanohablantes.
Ver AC Tool Pro LatinoMini Split Training
The full mini split course: how they work, maintenance, repair, sizing and install. 45 videos, quizzes and a certificate.
Mini Split Training (Paperback)
A 108-page full-color field manual with real photos, component testing, multi-zone, and 200+ practice questions.
Common questions
Do I need Type I as an HVAC tech?
If you only do residential and commercial split systems, Type II is the one you need. Type I is required for sealed-system work on refrigerators, window units, PTACs and the like. Universal covers both.
Is Type I easy?
It's the smallest section. Know the 90/80 rule, the 4-inch vacuum alternative and what counts as a small appliance, and you'll be in good shape.